128

Rockwell Automation Publication 2099-UM001D-EN-P - December 2012

Chapter 5

Configure and Startup the Kinetix 7000 Drive System

5. Observe the three status indicators on the front of the drive.

6. Observe the three SERCOS status indicators on the SERCOS module.

Status Indicator

Condition

Status

Do This

Drive

Off

Normal condition

Observe the Comm status LED.

Steady red

Drive is faulted

Go to Status Indicators on page

143

.

Comm

Flashing green

Establishing communication with network

Wait for steady green.

Steady green

Communication is ready

Observe the Bus status LED

Off

No ring present

Go to Interpret Error Codes and Status Indicators on page

138

.

Bus

Steady green

Axis is enabled when status should be disabled

1. Verify Hardware Enable Input (IOD-2) is open.
2. Verify MSO instruction is not commanded in RSLogix 5000

software.

3. Return to Apply Power to the Drive on page

126

.

Flashing green

(1)

Bus is up, axis is disabled (normal status)

Go to

step 6

.

Off

DC bus is not present

Go to Status Indicators on page

143

.

(1) The follower drive has a 2.5 second delay after DC bus voltage is applied before the Bus Status LED begins flashing. This provides the common bus leader time to complete precharge.

SERCOS Status Indicators

Status

Do This

Flashing green and red

Establishing communication

Wait for steady green on all three LEDs.

Steady green

Communication is ready

Go to Test and Tune the Axes on page

129

.

Not flashing green and red/
not steady green

SERCOS module is faulted

Go to the appropriate Logix manual for specific
instructions and troubleshooting.