Rockwell Automation Publication 2099-UM001D-EN-P - December 2012

27

Install the Kinetix 7000 Drive System

Chapter 2

Minimum Clearance Requirements

This section provides information to assist you in sizing your cabinet and
positioning your Kinetix 7000 system components.

Figure 7 - Minimum Clearance Requirements

See page

152

for power dissipation specifications.

IMPORTANT

Mount the module in an upright position as shown. Do not mount the
module on its side.

50.8 mm (2.0 in.) clearance right
of module is required

Minimum cabinet depth = 300 mm (11.8 in.)

Cable bend radius requires a minimum of
60 mm (2.4 in.) from the front panel connections.

101.6 mm (4.0 in.) clearance for

airflow and installation

50.8 mm (2.0 in.) clearance left

of module is required

101.6 mm (4.0 in.) clearance for

airflow and installation