Chapter 6

Troubleshoot the Kinetix 7000 Drive System

E69

DriveHardFault

Nonvolatile memory is corrupt due to control board hardware failure.

Load default parameters, save to nonvolatile
memory, and recycle power or reset the drive.

If fault persists, replace module.

E70

DriveHardFault

Nonvolatile memory is corrupt due to control board software error.

Load default parameters, save to nonvolatile
memory, and recycle power or reset the drive.

If fault persists, replace module.

E71

DriveHardFault

RAM or flash memory validation failure.

Cycle power.

If fault persists, replace module.

E72

DriveOvertemp Fault
(Drive Overtemp)

Inverter thermal switch
tripped

The drive fan failed.

Replace the failed module.

The cabinet ambient temperature is above
rating.

Check the cabinet temperature. See System Design
Guidelines o
n page

22

.

The machine duty cycle requires an RMS
current exceeding the continuous rating of
the controller.

Change the command profile to reduce speed or
increase time.

The airflow access to the Kinetix 7000 drive is
limited or blocked.

Check airflow and remove any fan blockage.

E76

DriveHardFault

DPI hardware initialization
fault detected.

Control board hardware failure.

Reset System.

If fault persists, replace system module.

E78

DriveHardFault
(Sercos Init)

Control hardware fault detected.

Cycle power.

If fault persists, replace module.

E80

DriveHardFault
(CPLD Flt)

Control hardware fault detected.

A-to-D conversion state machine error.

If fault persists, replace module.

E109

IGBT_TempFault

Junction temperature of Insulated Gate Bipolar Transistor exceeded.

Check for proper drive sizing.

Install larger kW rated drive.

E110

EEPROM_Fault

EEPROM failed.

EEPROM data corrupted or bus not calibrated.

If fault persists, replace module.

E111

Regen_PS_OK

The Regen_OK signal is missing at pins 7 and 8 of the GPIO connector.

Check error displays on RPS, and troubleshoot per
error message.

Reset system.

All others RESERVED.

Table 50 - Seven-segment Status Indicator Error Codes (Continued)

Error
Code

Fault Message RSLogix

Anomaly or Symptom

Potential Cause

Possible Resolution