Rockwell Automation 2099-BMxx Kinetix 7000 High Power Servo Drive User Manual User Manual

Page 148

Advertising
background image

148

Rockwell Automation Publication 2099-UM001D-EN-P - December 2012

Chapter 6

Troubleshoot the Kinetix 7000 Drive System

AuxFeedbackFault
(Aux Fdbk AQB)

E61

Auxiliary encoder has encountered an illegal state transition.

DISABLE DRIVE

No

AuxFeedbackFault
(Aux Fdbk Loss)

E62

The feedback wiring is open, shorted or missing.

DISABLE DRIVE

No

AuxFeedbackNoise
(Aux Fdbk Noise)

E63

Presence of noise on auxiliary feedback cable.

DISABLE DRIVE /
Feedback Noise

Yes

MotorFeedbackNoise
(Mtr Fdbk Noise)

E64

Presence of noise on motor feedback cable.

No Fault Message
(condition indicated by on-
screen message)
(Hookup Fault)

E65

Hookup procedure failed.

DISABLE DRIVE

No

No Fault Message
(condition indicated by on-
screen message)
(Atune Flt)

E66

Autotune procedure failed.

DISABLE DRIVE

No

DriveHardFault
(Task Init)

E67

Operating system failed.

SHUTDOWN

No

DriveHardFault
(SCANport Comm)

E68

DPI communication failed.

STOP MOTION

No

DriveHardFault
(Objects Init)

E69

Nonvolatile memory attribute out of range.

SHUTDOWN

No

DriveHardFault
(NV Mem Init)

E70

Nonvolatile memory corrupted.

SHUTDOWN

No

DriveHardFault
(Memory Init)

E71

RAM or flash memory validation failure.

SHUTDOWN

No

DriveOvertempFault
(Drive Overtemp)

E72

Inverter temperature limit exceeded. Firmware I

2

t protection does not generate a fault,

rather it dynamically folds back current when 110% of drive rating is reached.

SHUTDOWN

Yes

DriveHardFault
(Can Init)

E76

Either DPI or backplane CAN initialization failure.

SHUTDOWN

No

DriveHardFault
SERCOS Init

E78

Control hardware fault detected.

SHUTDOWN

No

HardwareFault
(CPLD FLT)

E80

Control hardware fault detected.

SHUTDOWN

No

IGBTTempFault
(IGBTFLT)

E109

Junction temperature of IGBT exceeded.

SHUTDOWN

No

EEPROMFault
(CPLD FLT)

E110

EEPROM failure. EEPROM data corrupt or bus not calibrated.

SHUTDOWN

No

RegenPSOK
(CPLD FLT)

E111

Regenerative PS+/- missing at GPIO.

SHUTDOWN

No

All Others RESERVED

(1) The Logix Motor Thermal Fault Action is tied to the motor thermostat fault. If this is set to Shutdown or Disable (in Logix), the drive will fold back the current when the I

2

T calculation indicates that the

motor temperature has exceeded 10% of its rated temperature. If it is set to Stop Motion or Status Only, the drive will not fold back the current. The I

2

T calculation never generates a fault.

Logix Fault Message
(HIM)

Error
Code

Description

Drive Fault Action/
Attribute

RSLogix
Programmable
Fault Action?