Determine the input power configuration, Grounded power configurations – Rockwell Automation 2099-BMxx Kinetix 7000 High Power Servo Drive User Manual User Manual

Page 75

Advertising
background image

Rockwell Automation Publication 2099-UM001D-EN-P - December 2012

75

Connect the Kinetix 7000 Drive System

Chapter 4

Determine the Input Power
Configuration

Before wiring input power to your Kinetix 7000 drive system you must determine
the type of input power to which you are connecting. The Kinetix 7000 drive is
configured at the factory to operate in a grounded power environment.

Grounded Power Configurations

Grounded (WYE) power wiring lets you ground your three-phase power at a
neutral point.

Figure 44 - Grounded Three-phase Power Wiring - WYE Secondary (Recommended)

ATTENTION: When using a LIM with your Kinetix 7000 drive, the AC line input
power must come from a grounded configuration.

When not using a LIM with your Kinetix 7000 drive, ungrounded configurations are
acceptable, but you must set the jumper to prevent high electrostatic build-up.

See Setting the Ground Jumper in Ungrounded Power Configurations on

page 78

for additional information.

L1

L2

L3

2099-BM08-S shown with

Lower Front Panel Removed

Transformer (WYE) Secondary

Three-phase

Input VAC

Phase Ground

Transformer

Bonded Cabinet

Ground

Ground Grid or

Power Distribution Ground

To Ground Stud

Line

Filter