Noise reduction guidelines for drive accessories – Rockwell Automation 2099-BMxx Kinetix 7000 High Power Servo Drive User Manual User Manual

Page 36

Advertising
background image

36

Rockwell Automation Publication 2099-UM001D-EN-P - December 2012

Chapter 2

Install the Kinetix 7000 Drive System

Table 6 - Line Interface Module

Table 7 - External Shunt Resistor Kit

Noise Reduction Guidelines for Drive Accessories

When mounting an AC (EMC) line filter or external shunt resistor refer to the
sections below for guidelines designed to reduce system failures caused by
excessive electrical noise.

AC Line Filters

Observe the following guidelines when mounting your AC (EMC) line filter.

See the

Establishing Noise Zones (AC Power)

on page

33

for an example.

Mount the ac line filter on the same panel as the Kinetix 7000 drive and as

close to the power input as possible.

Good HF bonding to the panel is critical.

For painted panels, refer to the examples on page 29.

Segregate input and output wiring as far as possible.

Wire/Cable

Connector

Zone

Method

Very
Dirty

Dirty

Clean

Ferrite
Sleeve

Shielde
d Cable

VAC line (main input)

IPL

X

230V AC input

APL

X

VAC load (shielded option)

OPL

X

X

VAC load (unshielded option)

X

Control power output

CPL

X

MBRK PWR, MBRK COM

P1L/PSL

X

Status I/O

IOL

X

Auxiliary 230V AC

P2L

X

Wire/Cable

Connector

Zone

Method

Very
Dirty

Dirty

Clean

Ferrite
Sleeve

Shielded
Cable

COL, DC+ (shielded option)

RC

X

X

COL, DC+ (unshielded option)

X

Thermal switch

TS

X

X

Fan (if present)

N/A

X

IMPORTANT

CE test certification applies only to ac line filter and single drive. Sharing a
line filter with multiple drives may perform satisfactorily, but the user takes
legal responsibility.

Advertising