Circuit breaker/fuse specifications, E circuit breaker/fuse specifications, Common dc bus fuse specifications – Rockwell Automation 2099-BMxx Kinetix 7000 High Power Servo Drive User Manual User Manual

Page 151

Advertising
background image

Rockwell Automation Publication 2099-UM001D-EN-P - December 2012

151

Specifications and Dimensions

Appendix A

Circuit Breaker/Fuse Specifications

While circuit breakers offer some convenience, there are limitations for their use.
Circuit breakers do not handle high current inrush as well as fuses.

Make sure the selected components are properly coordinated and meet
acceptable codes including any requirements for branch circuit protection.
Evaluation of the short-circuit available current is critical and must be kept below
the short-circuit current rating of the circuit breaker.

Use class CC, T, RK1, or J fuses, with current rating as indicated in the table
below. The following fuse examples and short-circuit current ratings are
recommended for use with the 2099-BM

xx-S drives when the Line Interface

Module (LIM) is not used.

Table 58 - 460V AC Input Drive Fuse and Motor Circuit Protector Specifications

Common DC Bus Fuse Specifications

Table 59 - Ferraz Shawmut Fuse Recommendations

IMPORTANT

LIM modules (catalog numbers 2094-BLxxS and 2094-XL75S-Cx) provide
branch circuit protection to the Kinetix 7000 drive. Follow all applicable NEC
and local codes.

Drive Cat. No.

Bussmann
Fuse

Dual Element Time Delay
Fuse (min/max)
A rms

Non-Time Delay
Fuse (min/max)
A rms

Motor Circuit
Protector (max)
A rms

2099-BM06-S

LPJ-90SP

50/90

50/150

50

2099-BM07-S

LPJ-110SP

60/110

60/200

70

2099-BM08-S

LPJ-125SP

80/125

80/250

100

2099-BM09-S

LPJ-200SP

125/200

125/300

125

2099-BM10-S

LPJ-250SP

150/250

150/500

150

2099-BM11-S

LPJ-400SP

225/400

225/600

250

2099-BM12-S

LPJ-500SP

300/550

300/700

400

Drive Cat. No.

Drive Current
Rating (Adc)

Recommended
Fuse

Fuse Current
Rating

i²t (A²Sec)

Peak Let-Through Current
at 100kA rms

Pre-Arc

Max. Clearing @
600V AC

2099-BM06-S

42.9

HSJ80

80

1600

15000

7000 A

2099-BM07-S

55.7

HSJ90

90

2300

21000

7400 A

2099-BM08-S

69.7

HSJ100

100

2700

23000

7700 A

2099-BM09-S

105

HSJ175

175

8000

60000

12000 A

2099-BM10-S

137

HSJ200

200

14000

92000

13000 A

2099-BM11-S

204

HSJ400

400

63000

450000

21000 A

2099-BM12-S

281

HSJ400

400

63000

450000

21000 A

Advertising