1756-MxxSE SERCOS Interface Module Noise Zones

Observe the following guidelines when installing your 1756-M

xxSE SERCOS

interface module.

The clean zone (C) is beneath the less noisy I/O modules (analog,

encoder, registration) - - (grey wireway).

The dirty zone (D) is above and below the power supply and noisy

modules (black wireway).

The SERCOS fiber-optic cables are immune to electrical noise.

Figure 13 - Establishing Noise Zones (ControlLogix)

D

D

C

AC Line

Filter

Spare Slot(s)

Dirty Wireway (D)

Clean Wireway (C)

Route dirty wireways directly above the ControlLogix rack

(shielded by the chassis).

Line Filter/Power Supply

Connections Segregated

(not in wireway)

Dirty I/O

(24V DC I/O, AC I/O)

Clean I/O

(Analog, Encoder

Registration)