Table 60 - Bussmann Fuse Recommendations

Contactor Ratings

The table below lists the recommended contactor ratings for Kinetix 7000 drives
installed without a Line Interface Module (LIM).

Power Dissipation
Specifications

Use this table to size an enclosure and calculate required ventilation for your
Kinetix 7000 drive system.

Drive Cat. No.

Drive Current
Rating (Adc)

Recommended
Fuse

Fuse Current
Rating

i²t (A²Sec)

Peak Let-Through Current
at 100kA rms

Pre-Arc

Max Clearing @
600V AC

2099-BM06-S

42.9

FWJ-80A

80

1550

9700

6300 A

2099-BM07-S

55.7

FWJ-100A

100

2800

17500

8000 A

2099-BM08-S

69.7

FWJ-125A

125

4800

35000

10000 A

2099-BM09-S

105

FWJ-175A

175

7500

65000

12000 A

2099-BM10-S

137

FWJ-200A

200

11700

80000

13000 A

2099-BM11-S

204

FWJ-500A

500

39500

329000

21000 A

2099-BM12-S

281

FWJ-500A

500

39500

329000

21000 A

Drive Cat. No.

Contactor

Safety Contactor

Coil Type

Coil Voltage Requirements

2099-BM06-S

100-C43DJ01

100S-C43-DJD4C

Standard with Diode

24V DC

2099-BM07-S

100-D95EN11

100S-D95EN22C

Electronic Coil

(1)

24V DC for control and 480V AC for coil power

2099-BM08-S

2099-BM09-S

2099-BM10-S

100-D140EN11

100S-D140EN22C

2099-BM11-S

100-D180EN11

100S-D180EN22C

2099-BM12-S

100-D250EN11

100S-D250EN22C

(1) Electronic coil control power requirements = 24V DC @ 15 mA.

Drive Cat. No.

Usage as a % of Rated Power Output

W

50%

100%

2099-BM06-S

294

465

2099-BM07-S

388

619

2099-BM08-S

452

730

2099-BM09-S

645

1072

2099-BM10-S

882

1479

2099-BM11-S

1275

2125

2099-BM12-S

1438

2437