Rockwell Automation Publication 2099-UM001D-EN-P - December 2012

125

Configure and Startup the Kinetix 7000 Drive System

Chapter 5

39. From the Bus Regulator Configuration pull-down menu, choose the

component appropriate for your actual hardware configuration. Note: The
Kinetix 7000 drive internal dynamic brake IGBT is not utilized by the
drive main control for bus regulation therefore any type of regulation must
come from an external source.

40. Click OK.
41. Repeat steps 1…27 for each additional axis.
42. Verify your Logix program and save the file.

Download the Program

After completing the Logix configuration you must download your program to
the Logix processor.

If your drive requires

Then choose

No bus regulator configuration

<none>

External Shunt configuration

1336-MOD-KB005, KB010 or KB050
1336-WB009, WB035 or WB110

(1)

(1) External shunt configuration 1336 MOD-KBxxx and 1336-WBxxx are no longer available for new sale but are selectable as

of this manual release.

External regeneration power supply

8720MC-RPS027, 8720MC-RPS065, or 8720MC-RPS190

(2)(3)(4)

(2) 8720MC-RPSxxx is an external regenerative converter system used to regulate the DC bus connected to the Kinetix 7000

drive. Selecting this device will require the Kinetix 7000 drive GPIO terminal block pins 7 and 8 to be wired. See

Figure 74

on page 165

for an example.

(3) 8720MC-RPS027BM-HV1 is no longer available for sale.
(4) 8720MC-RPS065BM-HV1 has been superseded by 8720MC-RPS065BM-HV2.