Safety engineering

Safe inputs and safe outputs

Safe inputs

7

114

EDSLCMX3024-SPS EN 5.0

7.4.3

Safe inputs

7.4.3.1

General

ƒ

Sensor type and sensor function cannot be parameterised.

ƒ

The sensor signals are converted into PROFIsafe bit information and transmitted to

the master control for processing. A local evaluation is not carried out.

ƒ

Unused sensor inputs must not be connected. The PROFIsafe bit of a non-connected

input is in the OFF state.

Note!

Make sure that an internal contact function test is carried out at the safe

inputs:
Safe input in the ON state

ƒ

A LOW level at one channel puts the input in the OFF state. The discrepancy

monitoring starts simultaneously.

ƒ

A LOW level must be detected at both channels within the discrepancy time,

otherwise a discrepancy error will be reported.

ƒ

To be able to confirm the discrepancy error, a LOW level must be detected

before at both channels.

Safe input in the OFF state

ƒ

A HIGH level at one channel starts the discrepancy monitoring.

ƒ

A HIGH level must be detected at both channels within the discrepancy

time, otherwise a discrepancy error will be reported.

ƒ

To be able to confirm the discrepancy error, a HIGH level must be detected

before at both channels.