Safety engineering
Safe inputs and safe outputs
Safe inputs
7
114
EDSLCMX3024-SPS EN 5.0
7.4.3
Safe inputs
7.4.3.1
General
ƒ
Sensor type and sensor function cannot be parameterised.
ƒ
The sensor signals are converted into PROFIsafe bit information and transmitted to
the master control for processing. A local evaluation is not carried out.
ƒ
Unused sensor inputs must not be connected. The PROFIsafe bit of a non-connected
input is in the OFF state.
Note!
Make sure that an internal contact function test is carried out at the safe
inputs:
Safe input in the ON state
ƒ
A LOW level at one channel puts the input in the OFF state. The discrepancy
monitoring starts simultaneously.
ƒ
A LOW level must be detected at both channels within the discrepancy time,
otherwise a discrepancy error will be reported.
ƒ
To be able to confirm the discrepancy error, a LOW level must be detected
before at both channels.
Safe input in the OFF state
ƒ
A HIGH level at one channel starts the discrepancy monitoring.
ƒ
A HIGH level must be detected at both channels within the discrepancy
time, otherwise a discrepancy error will be reported.
ƒ
To be able to confirm the discrepancy error, a HIGH level must be detected
before at both channels.