Commissioning, Code table – Lenze ELCAMZIxxx4SNNPSNN (LCU122) User Manual
Page 147
![background image](/manuals/566239/147/background.png)
Commissioning
Code table
8
147
EDSLCMX3024-SPS EN 5.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Designation
No.
C0016
Starting voltage U
0
0.0
{0.1 %}
100.0
= acceleration time
deactivated
1 Motor 1
40.0
2 Motor 2
40.0
C0040
Inhibit motor
starter
0
Inhibit motor starter (CINH)
Motor starter can only be
enabled if service switch is in
”ON” position
1
Enable motor starter (CINH)
C0043
TRIP reset
0
No fault active
Reset active fault via C0043 = 0
1
Fault active
C0052
Service code
Changes by Lenze service only!
C0054
uSEr
Apparent current of
motor 1
0
{A}
50 Read only
C0055
uSEr
Apparent current of
motor 2
0
{A}
50 Read only
C0061
Temperature in the
housing
0
{°C}
255 Read only
z
If C0061 > +80 °C:
– motor starter sets TRIP OH
C0093
Device type
4020
Read only
C0094
Reserved
C0099
Software version
x.y
Read only
x = main version, y = index
C0119
Configuration of
motor temperature
monitoring
Configures the PTC input.
Configuration of signal output in
C0415
1 Motor 1
1
PTC input active, TRIP effected
2 Motor 2
1
PTC input active, TRIP effected
0
PTC input inactive
1
PTC input active, TRIP effected
2
PTC input active, warning effected
C0120
uSEr
Rated motor
current
1.0
{0.1 A}
type-dependent Enter value from the motor
nameplate
1 Motor 1
1.0
2 Motor 2
1.0
C0121
Tripping class
Tripping characteristic see 19
1 Motor 1
2
Tripping class 10
2 Motor 2
2
Tripping class 10
0
I
2
t monitoring switched off
1
Tripping class 10A
2
Tripping class 10
3
Tripping class 20
4
Tripping class 30
C0122
Mains phase failure
message
0
0
TRIP
1
Warning
3
Off
C0123
I
2
t overload
message
0
0
TRIP
Change is only active after the
next enabling of the motor
starter
1
Warning
3
Off