Commissioning, Code table – Lenze ELCAMZIxxx4SNNPSNN (LCU122) User Manual

Page 147

Advertising
background image

Commissioning

Code table

8

147

EDSLCMX3024-SPS EN 5.0

IMPORTANT

Possible settings

Code

Selection

Lenze

Designation

No.
C0016

Starting voltage U

0

0.0

{0.1 %}

100.0

= acceleration time

deactivated

1 Motor 1

40.0

2 Motor 2

40.0

C0040

Inhibit motor

starter

0

Inhibit motor starter (CINH)

Motor starter can only be

enabled if service switch is in

”ON” position

1

Enable motor starter (CINH)

C0043

TRIP reset

0

No fault active

Reset active fault via C0043 = 0

1

Fault active

C0052

Service code

Changes by Lenze service only!

C0054
uSEr

Apparent current of

motor 1

0

{A}

50 Read only

C0055
uSEr

Apparent current of

motor 2

0

{A}

50 Read only

C0061

Temperature in the

housing

0

{°C}

255 Read only

z

If C0061 > +80 °C:

– motor starter sets TRIP OH

C0093

Device type

4020

Read only

C0094

Reserved

C0099

Software version

x.y

Read only

x = main version, y = index

C0119

Configuration of

motor temperature

monitoring

Configures the PTC input.

Configuration of signal output in

C0415

1 Motor 1

1

PTC input active, TRIP effected

2 Motor 2

1

PTC input active, TRIP effected

0

PTC input inactive

1

PTC input active, TRIP effected

2

PTC input active, warning effected

C0120
uSEr

Rated motor

current

1.0

{0.1 A}

type-dependent Enter value from the motor

nameplate

1 Motor 1

1.0

2 Motor 2

1.0

C0121

Tripping class

Tripping characteristic see  19

1 Motor 1

2

Tripping class 10

2 Motor 2

2

Tripping class 10

0

I

2

t monitoring switched off

1

Tripping class 10A

2

Tripping class 10

3

Tripping class 20

4

Tripping class 30

C0122

Mains phase failure

message

0

0

TRIP

1

Warning

3

Off

C0123

I

2

t overload

message

0

0

TRIP

Change is only active after the

next enabling of the motor

starter

1

Warning

3

Off