PROFIsafe on board

Parameter data transfer

DRIVECOM parameter data channel (DP-V0, cyclic)

6

60

EDSLCMX3024-SPS EN 5.0

6.4.1.2

Programming of write jobs

Step

Write job

1.

Define user data range of the motor starter, i.e. define the location of the PROFIBUS user data in the

host system (observe manufacturer-specific information).

2.

Enter the address of the desired parameter in the field ”Index and subindex“ (PROFIBUS output data).

3.

Enter parameter value in field ”Data/Error“.

4.

Job/service = write job and the ”Job/handshake“ bit must be changed (PROFIBUS output data).

5.

Check whether the ”Job/handshake“ bit is the same for the PROFIBUS input and output data. If the bit

”Job / handshake“ is the same, the response has been received. You should implement a time

monitoring.

6.

Check whether the ”Job/status“ bit is set:

z

If the ”Job/status“ bit is not set: The job was executed faultlessly

z

The ”Job/status“ bit is set:

The job has not been carried out correctly if the ”Job/status“ bit is set.

The error information is located in the field ”Data/error“.