5 safe profisafe connection, Safe profisafe connection, Safety engineering – Lenze ELCAMZIxxx4SNNPSNN (LCU122) User Manual
Page 125: Μc s sf
Safety engineering
Safety functions
Safe PROFIsafe connection
7
125
EDSLCMX3024-SPS EN 5.0
7.5.5
Safe PROFIsafe connection
7.5.5.1
Conditions
Condition for using the function:
ƒ
Software version 20
ƒ
PROFIBUS communication must be established. ( 42)
ƒ
PROFIsafe protocol according to ”PROFIsafe - Profile for Safety Technology”
specification, version 1.30, of the PROFIBUS user organsation (PUO)
ƒ
The device must receive PROFIBUS data telegrams from a master controller.
7.5.5.2
Response times
In order to detect the response time to a safety function request, the entire system must
be considered. The following is relevant:
ƒ
Response time of the connected sensors.
ƒ
Input delay of the safety inputs.
ƒ
Internal processing time.
ƒ
Monitoring time for the cyclic service in the PROFIBUS.
ƒ
Monitoring time of the PROFIsafe in the safety PLC.
ƒ
Processing time in the safety PLC.
ƒ
Delay times due to further components.
μC
μC
S
SF
t = 0
t
1
t
2
0
1
t
ps
t
4
2
PROFIBUS
t
3
t
5
lcu12x_352
Fig.7-6
Response times to the request of a safety function
Device
Drive-based safety
Safety PLC
μ
C Microcontroller
S
Safety sensor technology
SF Activated safety function