Technical data
Rated data
3
18
EDSLCMX3024-SPS EN 5.0
Note!
The motor starters are designed for rated currents between 1 A and 7 A.
If motors with rated currents < 1 A are operated on the motor starters, please
observe the following:
ƒ
The internal I
2
xt monitoring cannot be used because of the low current.
– Switch off the internal I
2
xt monitoring (C0121 = 0).
– Use a PTC or thermal contact (NC contact) to monitor the motor
temperature
– Appropriate external motor protection switches can be used in addition.
ƒ
The mains phase failure control can respond during operation, although no
main failure has occurred.
– Deactivate the mains phase failure control (C0122 = 3) to ensure that the
drive will not switch off with an error message.