Electrical installation

Important notes

5

22

EDSLCMX3024-SPS EN 5.0

5

Electrical installation

5.1

Important notes

Note!

ƒ

Please keep the plastic covers on the connectors for the control connections

and interfaces!

ƒ

Cover unused connections during transport, storage and operation with the

plastic covers to preserve the certified safety engineering features.

Danger!

ƒ

The X2x power connector contacts can conduct hazardous voltages if the

motor starter is connected to the mains. Therefore, disconnect the motor

starter before carrying out any work on it.

ƒ

All control terminals feature only basic insulation (single isolating distance)

following the connection of a PTC thermistor (PTC) or a thermal switch (NC

contact):

– Protection against accidental contact with defective isolating distance can

only be ensured through external measures, e.g. double insulation.

ƒ

To avoid injury to persons and breakdowns, it is essential that the motor

starter is properly earthed via X10!

Stop!

Ensure trouble-free operation of the motor starter:

ƒ

Avoid compensating currents via the PROFIBUS cable shield:

– For this, connect all devices with a 16 mm

2

cable via the FE bolts.

– Lay cable in parallel to bus cable.

– Use a copper braid cable to connect the FE bolts with the mounting

surface.

ƒ

Properly lock the connector plugs.