PROFIsafe on board

Parameter data transfer

PROFIdrive parameter data channel (PCW)

6

80

EDSLCMX3024-SPS EN 5.0

6.4.3.1

Programming of read jobs

Step

Read job

1.

Define the user data range of the motor starter, i.e. define the location of the user data in the host

system.

2.

Enter the address of the desired parameter in the field ”Index and subindex“ (output data).

3.

Job/Service = AK

4.

Job/Service = Read job

5.

Check whether index and subindex correspond with the job and whether the job identification is Û 0:

z

If the criteria are fulfilled, the desired motor starter data is transferred from the field “Parameter

value” to the master.

z

If these criteria are not met, the response identification is negative, i.e. high nibble of byte 1 = 7

hex

In this case the error information can be read out from the entry in the low word.

Example: Read parameter
The housing temperature (assumption: ϑ= 43° C)of the motor starter is to be read (C0061).

ƒ

Job identification (high nibble in byte 1)
– Read simple parameter: “1”

ƒ

Code: (low nibble in byte 1 and byte 2)
– C0061: 61 = 3D

hex

ƒ

Lenze subcode (byte 3):
– Subindex = 0, as there is no subindex under code C0061.

ƒ

Byte 5 ...8: Data (not contained in the request telegram)
– Data 1 to data 4 = 43° C x 10000 = 430000 = 00 06 8F B0

hex

Result:

ƒ

Request telegram from master to the motor starter

Byte 1*

Byte 1* +2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

Byte 8

AK

Code

Subcode

Reserved

Parameter value

1

hex

03D

hex

00

hex

00

hex

00

hex

00

hex

00

hex

00

hex

0001bin

000000111101 bin

00000000bin

00000000bin

00000000bin

00000000bin

00000000bin

00000000bin

Wait for response identification with code = 03D and subcode 0

ƒ

Response telegram from the motor starter to the master (for faultless execution)

Byte 1*

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

Byte 8

AK

Code

Subcode

Reserved

Parameter value

2

hex

03D

hex

00

hex

00

hex

00

hex

06

hex

8F

hex

B0

hex

0010

bin

000000111101 bin

00000000

bin

00000000

bin

0000 0000

bin

0000 0110

bin

1000 1111

bin

1011 0000

bin

Tab. 6-4

Telegram exchange in the PROFIdrive parameter data channel