PROFIdrive parameter data channel (DP-V1, acyclic)

Introduction
Data communication with PROFIBUS-DP-V0 is characterised by cyclic diagnostics and

cyclic process data and parameter data transfer.
Anoptional service extensionis theacyclic parameterdatatransferof PROFIBUS-DP-V1.All

standard services under PROFIBUS-DP-V0 still maintain their unrestricted validity.
PROFIBUS-DP-V0 and PROFIBUS-DP-V1 can be operated simultaneously in the same

network. This enables the step-by-step expansion or retrofitting of a system.
The services of PROFIBUS-DP-V1 can be used by the class 1 master (PLC) and the class 2

master (diagnostics master etc.).
The integration of the acyclic service into the fixed bus cycle depends on the corresponding

configuration of the class 1 master:

ƒ

For an existing configuration a time slot is reserved.

ƒ

Without configuration the acyclic service is appended when a class 2 master

acyclically accesses a DP-V1 slave.

Features

ƒ

Address for parameter number and subindex with a width of 16 bits each.

ƒ

Processing of one parameter request at a time (no pipelining).

ƒ

A parameter request/response must fit into a data block (max. 240 bytes).

Requests/responses cannot be split into several data blocks.

ƒ

Spontaneous messages are not transmitted.

ƒ

There are only acyclic parameter requests.

ƒ

Profile-specific parameters can be read independently of the slave state.