PROFIsafe on board

Establishing of PROFIBUS communication

Configuration of the host

6

45

EDSLCMX3024-SPS EN 5.0

Defining user data length
The user datalengthis defined during the PROFIBUS initialisation phase. You canconfigure

up to 10 process data words.
Optionally you can activate a parameter data channel. If the parameter data channel is

active, it additionally occupies 4 words of the process input and process output data.

ƒ

PIW: process data input word
(process data from the motor starter to the master)

ƒ

POW: process data output word
(process data from the master to the motor starter)

The user data lengths for process input data and process output data are identical. The

selection takes place via identification bytes in the configuration software for the

PROFIBUS system.

Parameter data channel

Process data channel

Without /

with

Identification / user data length

Identification / user data length

Without

-

z

Identification

– without consistency: 70

hex

... 79

hex

(112 ... 121)

– with consistency: F0

hex

... F9

hex

(240 ... 249)

z

User data length: 1 ... 10 words

(POW/PIW 1 ... POW/PIW 10)

With

z

Identification: F3

hex

(243)

z

User data length: 4 words

(word 1 ... word 4)

z

Identification

– without consistency: 70

hex

... 79

hex

(112 ... 121)

– with consistency: F0

hex

... F9

hex

(240 ... 249)

z

User data length: 1 ... 10 words

(POW/PIW 1 ... POW/PIW 10)

General structure of the identification byte

MSB

LSB

7

6

5

4

3

2

1

0

User data length

00 1 (byte / word)

...

15 16 (bytes / words)

Input/Output

00 Specific identification format

01 Input

10 Output

11 Input and output

Length/Format

0 Byte

1 Word

Consistency

0 Byte or word

1 Total length

Advertising