Safety engineering – Lenze ELCAMZIxxx4SNNPSNN (LCU122) User Manual

Page 134

Advertising
background image

Safety engineering

Safety functions

Safe PROFIsafe connection

7

134

EDSLCMX3024-SPS EN 5.0

Diagnostic information

Error number

Description

64

The Profisafe target address set does not comply with the parameter F_Dest_Add.

65

The F_Dest_Add parameter has the invalid value 0x0000 or 0xFFFF.

66

The F_Source_Add parameter has the invalid value 0x0000 or 0xFFFF.

67

The F_WD_Time parameter has the invalid value 0 ms.

68

The F_SIL parameter does not have the valid value 0 ... 2.

69

The F_CRC_Length parameter does not have the valid value 2.

70

The version of the PROFIsafe parameter set is wrong.

71

CRC1 error

Tab. 7-16

Information contents of byte 11