Safety engineering
Safety functions
Safe PROFIsafe connection
7
134
EDSLCMX3024-SPS EN 5.0
Diagnostic information
Error number
Description
64
The Profisafe target address set does not comply with the parameter F_Dest_Add.
65
The F_Dest_Add parameter has the invalid value 0x0000 or 0xFFFF.
66
The F_Source_Add parameter has the invalid value 0x0000 or 0xFFFF.
67
The F_WD_Time parameter has the invalid value 0 ms.
68
The F_SIL parameter does not have the valid value 0 ... 2.
69
The F_CRC_Length parameter does not have the valid value 2.
70
The version of the PROFIsafe parameter set is wrong.
71
CRC1 error
Tab. 7-16
Information contents of byte 11