8
149
EDSLCMX3024-SPS EN 5.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Designation
No.
C0150
Motor starter
status word 1
(parameter
channel)
Request of the status via parameter channel. The
most important status information units are
summarised as bit patterns
z
Some bits in C0417 are freely
connectable with internal
digital signals
z
In the diagnosis terminal:
read only (hexadecimal)
Bit
Assignment
0
Image of C0417/1
1
Image of C0417/2
2
Image of C0417/3
3
Image of C0417/4
4
Image of C0417/5
5
Image of C0417/6
6
Image of C0417/7
7
Motor starter enabled/inhibited
0 Motor starter enabled
1 Motor starter inhibited
11|10|9|8 Device state
0011 Operation inhibited
0110 Operation enabled
1000 Fault active
12
Motor starter overtemperature warning
0 Temperature in the housing < 75 °C
1 Temperature in the housing > +75 °C
13
Image of C0417/14
14
Image of C0417/15
15
Image of C0417/16
C0151
Motor starter
status word 2
(parameter
channel)
Bit
Assignment
z
The bits in C0418 are freely
connectable with internal
digital signals
z
In the diagnosis terminal:
read only (hexadecimal)
0
Image of C0418/1
...
...
15
Image of C0418/16
C0156
Current threshold
0
{1 %}
150 Programmable current threshold
Configuration of signal output in
C0415
1 Motor 1
0
Reference: rated motor current
in C0120/1
2 Motor 2
0
Reference: rated motor current
in C0120/2
C0161
Current error
Display of history buffer
contents
Diagnosis terminal: three-digit
alphanumeric fault
identification
C0162
Last error
C0163
Last but first error
C0164
Last but second
error
C0165
Service code
LECOM