PROFIsafe on board

Parameter data transfer

DRIVECOM parameter data channel (DP-V0, cyclic)

6

59

EDSLCMX3024-SPS EN 5.0

Example: read parameter
The housing temperature (assumption: ϑ= 43° C)of the motor starter is to be read (C0061).

ƒ

Byte 1: job

Bit 7

0

M u N N M M M N

“1” (read)

(reserved)

“3”(= data length 4 bytes)

Handshake

Status, only relevant for response telegram

ƒ

Byte 2: subindex

Subindex = 0, as there is no subindex under code C0061.

ƒ

Byte 3/4: index (calculation)

Index (of the read request) = 24575 - code no.
Index = 24575 - 61 = 24514 = 5F C2

hex

(5F

hex

= bigh byte, C2

hex

= low byte)

ƒ

Byte 5 ...8: data (contained in the response telegram)

Data 1 to data 4 = 43° C x 10000 = 430000 = 00 06 8F B0

hex

Result:

ƒ

Request telegram from master to the motor starter

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

Byte 8

Service

Subindex

Index

(high byte)

Index

(low byte)

Data 4

Data 3

Data 2

Data 1

01

hex

00

hex

5F

hex

C2

hex

00

hex

00

hex

00

hex

00

hex

00000001 bin

00000000bin

01011111 bin

11000010 bin

00000000bin

00000000bin

00000000bin

00000000bin

Wait for change of handshake bit (bit 6 here: 0 Æ 1) in the response

ƒ

Response telegram from the motor starter to the master (for faultless execution)

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

Byte 8

Service

Subindex

Index

(high byte)

Index

(low byte)

Data 4

Data 3

Data 2

Data 1

30

hex

00

hex

5F

hex

C2

hex

00

hex

06

hex

8F

hex

B0

hex

0011 0000

bin

0000 0000

bin

0101 1111

bin

1100 0010

bin

0000 0000

bin

0000 0110

bin

1000 1111

bin

1011 0000

bin

Tab. 6-2

Telegram exchange in the parameter data channel