Electrical installation

Safety engineering

5

33

EDSLCMX3024-SPS EN 5.0

Detail characteristics of the safe inputs and safe outputs
Signal

Specification

Min.

Typ.

Max.

I1A, I1B

I2A, I2B

I3A, I3B

I4A, I4B

PLC input, IEC-61131-2, 24 V, type 1
LOW signal

[V]

-3

0

5

Input current

[mA]

15

HIGH signal

[V]

15

24

30

Input current

[mA]

2

15

Input capacitance

[nF]

3.3

Switch-off time (depending on the standard device)

[ms]

2

4

Switch-on time

[ms]

2

4

Input delay (tolerated test pulse)

[ms]

1

CLA, CLB

PLC output, IEC-61131-2, 24 V DC, 50 mA
Supply voltage of the outputs

[V]

18

24

30

LOW signal

[V]

0

0.8

HGH signal

[V]

17

24

29

Output current

[mA]

50

Width of test pulse

[μs]

750

Frequency of test pulse

[s]

1

1.8

3

Specific resistance of a passive sensor

[kΩ]

2

O1A, O1B

O2A, O2B

PLC output, IEC-61131-2, 24 V DC, short-circuit-proof
Supply voltage of the outputs

[V]

18

24

30

Output voltage for LOW signal

[V]

0

0.8

Output voltage for HIGH signal

[V]

17

24

29

Output current

[mA]

500

Width of test pulse

[μs]

750

900

Frequency of test pulse

[s]

1

1.8

3