Safety engineering
Safety functions
Safe PROFIsafe connection
7
132
EDSLCMX3024-SPS EN 5.0
Status byte
Only the bits specified of the PROFIsafe status byte are supported:
Offset
Bit
Byte
7
6
5
4
3
2
1
0
4
-
-
-
FV_activated
COM-Failure
WD-Timeout
COM-Failure
CRC
-
-
Tab. 7-13
Structure of the PROFIsafe status byte
Details of the status byte
Name
Value
Description
COM-Failure
CRC
0
Status is not active.
1
Status after communication error is active.
COM-Failure
WD-Timeout
0
Status is not active.
1
Status after time-out is active.
FV_activated 0
The function is not active.
1
The PROFIsafe input data is deactivated.
-
0
Reserved for future extensions
Tab. 7-14
Detail specification of the status byte