Communication

5

40

EDSLCMX3024-SPS EN 5.0

Baud rate / bus cable length

Baud rate [kbps]

Length [m]

9.6 - 93.75

1200

187.5

1000

500

400

1500

200

3000 - 12000

100

Note!

Ensure that the baud rate depending on the amount of data, cycle time and

number of stations is only selected as high as required for the application.

Specification of the transmission cable
Please follow the specifications of the PROFIBUS user organisation (PUO) for signal cables:

Bus cable specification
Specific resistance

135 - 165 Ω/km, (f = 3 - 20 MHz)

Capacitance per unit length

30 nF/km

Loop resistance

< 110 Ω/km

Core diameter

> 0.64 mm

Core cross-section

> 0.34 mm

2

Cores

Double twisted, insulated and shielded