Profisafe on board, Parameter response for faultless transmission, Parameter response for faulty transmission – Lenze ELCAMZIxxx4SNNPSNN (LCU122) User Manual
Page 74
PROFIsafe on board
Parameter data transfer
PROFIdrive parameter data channel (DP-V1, acyclic)
6
74
EDSLCMX3024-SPS EN 5.0
Parameter response for faultless transmission
Byte 1
Byte 2
Byte 3
Byte 4
Request reference:
0xXX
Response
identifier:
0x81
Axis:
0x00
Number of
indexes:
0x01
(Mirrored)
Parameter read
(Mirrored)
Byte 5
Byte 6
Format:
0x43
Number of values:
0x01
Double word
1 value
Byte 7
Byte 8
Byte 9
Byte 10
High word
Low word
High byte
Low byte
High byte
Low byte
Value:
0x00
0x06
0x8F
0xB0
Value: 43 S 10000 = 430000 = 0x68FB0
Parameter response for faulty transmission
Byte 1
Byte 2
Byte 3
Byte 4
Request reference:
0xXX
Response
identifier:
0x81
Axis:
0x00
Number of
indexes:
0x01
Mirrored
Parameter not
read
Mirrored
Byte 5
Byte 6
Format:
0x44
Number of values:
0x01
Error
Byte 7
Byte 8
0x00
0xXX
Error code, see ”Error code list”