Parameter data transfer

DRIVECOM parameter data channel (DP-V0, cyclic)

6

54

EDSLCMX3024-SPS EN 5.0

6.4.1

DRIVECOM parameter data channel (DP-V0, cyclic)

Addressing of the Lenze parameters
For the DRIVECOM parameter data channel, the parameters of a device are not addressed

directly via Lenze code numbers, but via indexes (byte 3 / byte 4) and subindexes (byte 2).
The Lenze code numbers are converted into indexes via an offset (24575

dec

or 5FFF

hex

):

Addressing of the Lenze codes

Example for C0001 (operating mode)

– PROFIBUS index =

24575 - Lenze code number

– PROFIBUS index =

24575 - 1 = 24574

– PROFIBUS index

hex

=

5FFF

hex

- Lenze code number

hex

– PROFIBUS index

hex

=

5FFF

hex

- 1

hex

= 5FFE

hex

Lenze parameters are mainly represented in the fixed point format, data type integer32

with four decimal digits. For this reason, the value of the parameter or the value of the code

must be multiplied by 10000 in order to obtain integer values.
This parameter value is entered into the user data (byte 5 - byte 8) of the telegram.

Telegram structure

(overview)
The telegram of the DRIVECOM parameter data channel consists of a total of 8 bytes. The

individual bytes are described in detail on the following pages.

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

Byte 8

Service

Subindex

Index

High byte

Index

Low byte

Data 4 /

Error 4

Data 3 /

Error 3

Data 2 /

Error 2

Data 1 /

Error 1