Safety engineering

Safety functions

Safe PROFIsafe connection

7

130

EDSLCMX3024-SPS EN 5.0

Control byte
Only the bits specified of the PROFIsafe control byte are supported:

Offset

Bit

Byte

7

6

5

4

3

2

1

0

4

-

-

-

activate

_FV

-

-

-

-

Tab. 7-9

Structure of the PROFIsafe control byte

Details of the control byte
Name

Value

Description

activate_FV

1

The PROFIsafe output data is deactivated. Thus, the STO function is activated.

0

The function is deactivated.

-

0

Reserved for future extensions

Tab. 7-10

Detail specification of the control byte