Commissioning, Code table – Lenze ELCAMZIxxx4SNNPSNN (LCU122) User Manual
Page 148
![background image](/manuals/566239/148/background.png)
Commissioning
Code table
8
148
EDSLCMX3024-SPS EN 5.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Designation
No.
C0126
Behaviour in case
of communication
error
2
Monitored communication channel
0
All monitoring is deactivated
1
Reserved
2
Monitoring of internal communication
active
A communication abort with
activated monitoring initiates
TRIP CE5
4
Reserved
8
Reserved
C0135
Motor starter
control word
(parameter
channel)
Control of the motor starter via parameter channel.
The most important control commands are
summarised in bit commands
C0135 cannot be changed by
means of the diagnosis terminal
Bit
Assignment
0
Motor 1 start/stop
0 Stop motor 1
1 Start motor 1
1
Motor 2 start/stop or selection of
direction of rotation
0 Stop motor 2 or CCW rotation
1 Start motor 2 or CW rotation
2
Control of brake 1
0 Engage brake 1
1 Release brake 1
3
Control of brake 2
0 Engage brake 2
1 Release brake 2
4 ... 5
Reserved
6
Selection of mains-side field rotation
direction
Only active for motor starter
ELCAMZI as of SW 3.4
0 Clockwise rotating field
1 Anti-clockwise rotating field
7 ... 8
Reserved
9
Enable/inhibit motor starter
0 Enable motor starter
1 Inhibit motor starter
10
TRIP set
Sets fault ”external error” (EEr ,
LECOM No. 91)
0 External error active
1 No fault
11
TRIP reset
Cause of malfunction has to be
eliminated
1 ⇒ 0 Edge resets fault
12
Reserved
...
15