2 malfunction of the drive, Troubleshooting and fault elimination – Lenze ELCAMZIxxx4SNNPSNN (LCU122) User Manual

Page 162

Advertising
background image

Troubleshooting and fault elimination

Malfunction of the drive

9

162

EDSLCMX3024-SPS EN 5.0

9.2

Malfunction of the drive

Fault

Possible cause

Remedy

PROFIBUS master indicates

bus error and LED

”STATUS FB” = off

Short circuit/open circuit

Check PROFIBUS wiring

Bus termination not connected

Connect bus terminating resistor of the last

bus device.

Incorrect station address

Set correct station address.

PROFIBUS master indicates

bus error and LED

”STATUS FB” blinking

Incorrect PROFIBUS configuration

data

Check the configuration data sent by the

master under C1526.

Permitted configuration data:

45

PROFIBUS master indicates

PROFIsafe error

(LED ”PS” = on)

Master is configured incorrectly

Use current GSE file.

PROFIBUS master indicates

PROFIsafe error

(LED ”PS” = on,

LED ”ME” = off)

Incorrect PROFIsafe destination

address

Set the correct PROFIsafe destination

address in C1570.

Incorrect GSE file loaded

Use current GSE file.

Controller cannot be

enabled

Not enabled via control word

Send value ”0” to device control (see

FIF-CTRL1, bit 0)

Controller inhibit via service switch

active

Set service switch in ON position

Drive does not start,

LED ”ME” = off,

drive enabled via PROFIsafe

Discrepancy error on the safe inputs

(LED ”ME” is blinking after 30 s.)

Eliminate discrepancy

Drive is not running

service switch = ON

LED ”Serv” = off

LED ”Run” blinking

Overload on the inputs and outputs,

total current > 1.3 A

1. Reduce total current on all inputs and

outputs.

2. Acknowledge all pending errors in the

master control.

3. Enable drive.