Technical data

Rated data

3

19

EDSLCMX3024-SPS EN 5.0

I

2

t tripping characteristic:

According to DIN EN 60947-4-2 (AC semiconductor motor controllers and starters)

0.01

0.1

1

10

100

1000

10000

0.02

t [s]

1.05

2

3

4

5

6

7.2

8

I/I

r

Class 10A

Class 10

Class 20

Class 30

start031

Tripping classes
Class 10A

Tripping classes, can be set in C0121

Class 10

= Lenze setting

Class 20
Class 30
I

= Output current

I

r

= Rated motor current, can be set in C0120

Example for

Class 10:

The motor starter shuts down with an error message, if the output current I measures 4 times

the set rated motor current I

r

for approx. 13 s.

Note!

Regardless of the tripping class set, the motor starter always shuts down if the

output current I measures 8 times the set rated motor current I

r

for 20 ms.