Commissioning, Code table – Lenze ELCAMZIxxx4SNNPSNN (LCU122) User Manual

Page 154

Advertising
background image

Commissioning

Code table

8

154

EDSLCMX3024-SPS EN 5.0

IMPORTANT

Possible settings

Code

Selection

Lenze

Designation

No.
C0415

uSEr

Configuration of

digital output

signals

Output of internal digital signals on

terminals

1 Digital output A1

3

Status of motor 1

Motor 1 is running

HIGH

Motor 1 is stopped

LOW

2 Digital output A2

4

Status of motor 2 or direction of rotation

Motor 2 is running or

CCW rotation

HIGH

Motor 2 is stopped or

CW rotation

LOW

Internal digital signals

0

Not assigned

1

PAR-B0 active

2

Motor starter inhibited

3

Status of motor 1

4

Status of motor 2 or direction of rotation

5

Status of brake 1

Brake released

HIGH

Brake engaged

LOW

6

Status of brake 2

Brake released

HIGH

Brake engaged

LOW

7

Error in the power section

8

Motor starter enabled/inhibited

9 ... 12

Reserved

13

Warning “Overtemperature in the

housing”

14

Manual operation active

15

Status of service switch

”ON”

HIGH

”OFF”

LOW

16

Ready for operation

17

PAR-B1 active

18

Warning “Overtemperature of motor 1”

(PTC input)

Is only generated if C0119/1 = 2

19

Warning “Overtemperature of motor 2”

(PTC input)

Is only generated if C0119/2 = 2

20

Apparent current (C0054) < current

threshold (C0156/1)

V-belt monitoring of motor 1

21

Apparent current (C0055) < current

threshold (C0156/2)

V-belt monitoring of motor 2