Commissioning, Code table – Lenze ELCAMZIxxx4SNNPSNN (LCU122) User Manual
Page 154
![background image](/manuals/566239/154/background.png)
Commissioning
Code table
8
154
EDSLCMX3024-SPS EN 5.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Designation
No.
C0415
uSEr
Configuration of
digital output
signals
Output of internal digital signals on
terminals
1 Digital output A1
3
Status of motor 1
Motor 1 is running
HIGH
Motor 1 is stopped
LOW
2 Digital output A2
4
Status of motor 2 or direction of rotation
Motor 2 is running or
CCW rotation
HIGH
Motor 2 is stopped or
CW rotation
LOW
Internal digital signals
0
Not assigned
1
PAR-B0 active
2
Motor starter inhibited
3
Status of motor 1
4
Status of motor 2 or direction of rotation
5
Status of brake 1
Brake released
HIGH
Brake engaged
LOW
6
Status of brake 2
Brake released
HIGH
Brake engaged
LOW
7
Error in the power section
8
Motor starter enabled/inhibited
9 ... 12
Reserved
13
Warning “Overtemperature in the
housing”
14
Manual operation active
15
Status of service switch
”ON”
HIGH
”OFF”
LOW
16
Ready for operation
17
PAR-B1 active
18
Warning “Overtemperature of motor 1”
(PTC input)
Is only generated if C0119/1 = 2
19
Warning “Overtemperature of motor 2”
(PTC input)
Is only generated if C0119/2 = 2
20
Apparent current (C0054) < current
threshold (C0156/1)
V-belt monitoring of motor 1
21
Apparent current (C0055) < current
threshold (C0156/2)
V-belt monitoring of motor 2