Electrical installation, Basic circuit diagram for reversing operation – Lenze ELCAMZIxxx4SNNPSNN (LCU122) User Manual

Page 26

Advertising
background image

Electrical installation

Basic circuit diagram

ELCAMZIxxx4SNNPSNN motor starter

5

26

EDSLCMX3024-SPS EN 5.0

Basic circuit diagram for reversing operation

M

3~

-

+

~

~

S1

S2

1

2

3

4

5

6

1

2

3

Th

BRK1

X21

c

a

U1

V1

W1

1

2

3

a

X10

S0

STO

BS1

PE

4 * 2.5 mm

2

PE

PE

F1
16 A

K2

3/PE AC 400 V

PE

PE

L3

L2

L1

M

3~

-

+

~

~

S1

S2

1

2

3

4

5

6

1

2

3

Th

BRK2

a

U1

V1

W1

BS2

FE

PE

PE

X60

FE

FE

PROFIsafe

PROFIsafe

PE

X32

X31

X22

1

2

3

b

μC

X11

~

24 V DC

+

-

N

c

K10

K1

lcu122_010

F1

Cable protection
Observe cable protection standards for fuse dimensioning!

K1

Main contactor

K10

Contactor relay: Changeover between normal operation and reversing operation

K2

Contactor for 24 V supply

FE

Functional earth for compliance with EMC conditions, prevents compensating currents

via the PROFIBUS cable shield

S0

Service switch

BS1

Brake control, motor 1

BRK1

Spring-operated brake, motor 1

BS2

Brake control, motor 2

BRK2

Spring-operated brake, motor 2

Th

PTC thermistor (PTC) or thermal contact (NC contact)

STO

Safe torque off via PROFIsafe

Advertising
This manual is related to the following products: