Profisafe on board, Code table diagnostics, C1526: display of last configuration data – Lenze ELCAMZIxxx4SNNPSNN (LCU122) User Manual
Page 98: Type of the parameter data channel set, Length of the process data, Process data with or without consistency, Observe the descriptions, For the user data length ( 45), For the meaning of consistency ( 102)
PROFIsafe on board
Code table
Diagnostics
6
98
EDSLCMX3024-SPS EN 5.0
C1526:
Display of last configuration data
Code
Subcode
Index
Possible settings
Data type
Lenze
Selection
C1526
1: 1st byte
2: 2st byte
3: 3st byte
23049
d
=
5A09
h
0
[1]
65535 FIX32
This code shows the current configuration frame that has been selected via the GSE file in
the PROFIBUS master.
On the basis of the configuration data, the following can be read (see table below):
ƒ
Type of the parameter data channel set
ƒ
Length of the process data
ƒ
Process data with or without consistency
Consistent
channel
+ PCD ...
Subcode
Values
Description
Safety (4W)
4 words without consistency
Drivecom-PAR (Cons)
PCD(1W)
1
F3
hex
With a consistent DRIVECOM parameter data channel and process data
2
70
hex ...
79
hex
With a consistent DRIVECOM parameter data channel and process data
Process data without consistency
70
hex:
1 word ... 79
hex
: 10 words
PZD(1W cons)
1
F3
hex
With a consistent DRIVECOM parameter data channel and consistent
process data
2
F0
hex ...
F9
hex
With a consistent DRIVECOM parameter data channel and consistent
process data
Process data with consistency
F0
hex:
1 word ... F9
hex
: 10 words
PCW(Cons)
PCD(1W)
1
00
hex
With a consistent PROFIdrive parameter data channel and process data
2
F3
hex
With a consistent PROFIdrive parameter data channel and process data,
byte 1 in this case is 00
hex
3
70
hex ...
79
hex
With a consistent PROFIdrive parameter data channel and process data
Process data without consistency
70
hex:
1 word ... 79
hex
: 10 words
PCD(1W cons)
1
00
hex
With a consistent PROFIdrive parameter data channel and consistent
process data
2
F3
hex
With a consistent PROFIdrive parameter data channel and consistent
process data, byte 1 in this case is 00
hex
3
F0
hex ...
F9
hex
With a consistent PROFIdrive parameter data channel and consistent
process data
Process data with consistency
F0
hex:
1 word ... F9
hex
: 10 words
PCD(1W)
1
70
hex ...
79
hex
Process data without consistency
70
hex:
1 word ... 79
hex
: 10 words
PCD(1W cons)
F0
hex ...
F9
hex
Process data with consistency
F0
hex:
1 word ... F9
hex
: 10 words
Tip!
Observe the descriptions
ƒ
for the user data length ( 45)
ƒ
for the meaning of consistency ( 102)