Safety engineering
Safe inputs and safe outputs
Safe inputs
7
115
EDSLCMX3024-SPS EN 5.0
Specification
Sensor type
Passive
Active
Discrepancy time
30 s
Input delay
4 ms
0 ms
Input filter time for test pulses
15 ms
Repetition rate of the test pulses
Is defined by the clock outputs CLA
and CLB
> 50 ms
Error response
EC_S0
Confirmation via PROFIsafe
Tab. 7-2
Specification of the sensor connections
Explanations
Discrepancy time
ƒ
Maximum time in which both channels of a safe input may have non-equivalent
states without the safety engineering noticing an error.
Input delay
ƒ
Time between the recognition of the signal change and the effective evaluation of
an input signal. As a result, multiple and short signal changes due to contact bounce
of the components are not taken into account.
Input filter time
ƒ
Time in which the interference pulses and test pulses are not detected by e.g. active
sensors that are switched on.