Commissioning

Switching over between normal operation and reversing operation

8

143

EDSLCMX3024-SPS EN 5.0

8.4

Switching over between normal operation and reversing operation

Note!

The reversing operation is exclusively designed for changing the direction of

rotation under special circumstances. E.g. for withdrawing the drive from a

limit position.
The reversing operation cannot be used to change the direction of rotation

during operation.

Step

Operation

Comment

See

Switching over from normal operation to reversing operation:
Reversing operation has to be configured.

C0410/7 has to be connected to an

external signal source.

1. Stop both motors.

C0410/1 = LOW, C0410/2 = LOW

2. Apply the brakes if required.

C0410/3 = LOW, C0410/4 = LOW

3. Inhibit the motor starter.

C0040 = 0

4. Switch off the mains supply.

Open the contactor K1.

5. Activate revering operation.

C0410/7 = HIGH

HIGH = anti-clockwise rotating field

6. Wait for at least 1 second!
7. Switch over mains-side rotating

field.

Switch over the contactor K10 to the

anti-clockwise rotating field.

26

8. Switch on the mains supply.

Close the contactor K1.

The active rotating field can be

determined via the status signal

”Active mains-side rotating field”.

(See C0415)

9. Enable the motor starter.

C0040 = 1

10. Release the brakes if required.

C0410/3 =HIGH, C0410/4 = HIGH

11. Traverse the drive in opposite

direction.

C0410/1 = HIGH, C0410/2 = HIGH

E.g. for withdrawing the drive from

a limit position.

Switching over from reversing operation to normal operation:
1. Stop both motors.

C0410/1 = LOW, C0410/2 = LOW

2. Apply the brakes if required.

C0410/3 = LOW, C0410/4 = LOW

3. Inhibit the motor starter.

C0040 = 0

4. Switch off the mains supply.

Open the contactor K1.

5. Activate normal operation.

C0410/7 = LOW

LOW = clockwise rotating field

6. Wait for at least 1 second!
7. Switch over mains-side rotating

field.

Switch over the contactor K10 to the

clockwise rotating field.

26

8. Switch on the mains supply.

Close the contactor K1.

The active rotating field can be

determined via the status signal

”Active mains-side rotating field”.

(See C0415)

9. Enable the motor starter.

C0040 = 1

10. Release the brakes if required.

C0410/3 =HIGH, C0410/4 = HIGH

11. Start the drive.

C0410/1 = HIGH, C0410/2 = HIGH