Commissioning

Before switching on

8

141

EDSLCMX3024-SPS EN 5.0

8.2

Before switching on

Stop!

Short circuits or earth faults in the wiring destroy the motor starter. Check the

wiring with regard to short circuits and earth faults.

In order to prevent injury to persons or damage to material assets, check ...

ƒ

... the wiring with regard to completeness, short circuits and earth faults.

ƒ

... the ”Emergency-off” function of the entire system.

ƒ

... whether the rated motor current is set correctly.

In order to ensure the enclosure IP54, you have to ...

ƒ

... close all connectors on the motor starter that are not used by means of blanking

plugs.

ƒ

... close the AIF interface (X70) by using the supplied rubber cover.

In order to prevent faults of the PROFIBUS communication, you have to ...

ƒ

... activate the bus terminating resistor on the physically first and last node.