Profisafe on board – Lenze ELCAMZIxxx4SNNPSNN (LCU122) User Manual
Page 50
![background image](/manuals/566239/50/background.png)
PROFIsafe on board
Process data transfer
Device control
6
50
EDSLCMX3024-SPS EN 5.0
The bit assignments for the applicable control word 1 (FIF-CTRL1) can be gathered from the
following table:
FIF control word 1 (FIF-CTRL1)
Bit
Assignment
0
S1 (motor 1 start/stop)
0
1
Stop motor 1
Start motor 1
1
S2 (motor 2 start/stop or selection of direction of rotation)
0
1
Stop motor 2 or CCW rotation
Start motor 2 or CW rotation
2
Brake 1 (control of brake 1)
3
Brake 2 (control of brake 2)
4
Reserved
5
Reserved
6
Reserved
7
Reserved
8
Reserved
9
Controller inhibit (FIF-CTRL1-CINH)
0
1
Enable motor starter
Inhibit motor starter
10
External fault
(FIF-CTRL1-TRIP-SET)
0
1
External error active
No fault
11
Fault reset
0=>1
(FIF-CRTL1-TRIP-RESET)
Bit change causes trip reset
12
Reserved
13
Reserved
14
Reserved
15
Reserved