Grounding Practices (cont.)

Grounding Requirements and Grounding Specification for

Customers and Power Integrators

An external ground must be attached to the main ground bus. The
grounding means must comply with applicable local codes and
standards. As general guidelines, for information only, the ground
path must be of sufficiently low impedance and capacity that:

• the rise in potential of the drive ground point when subjected to a

current of twice the rating of the supply should be no higher than
4 volts over ground potential.

• the current flowing into a ground fault will be of sufficient

magnitude to cause the protection to operate.

The main grounding conductor(s) should be run separately from
power and signal wiring so that faults:

• do not damage the grounding circuit,

or

• will not cause undue interference with or damage to protection or

metering systems, or cause undue disturbance on power lines.