Component Definition and Maintenance 6-57
7000 “C” Frame
7000L-UM300I-EN-P – June 2013
+15V - SPGDB TEST
3 phase, 4 wire
XXXVAC
+24V I/O
3phase
TX, XXXV/208V
XXX = 380, 480, 600
DC
FAIL
AC
FAIL
C hold-up
DC/DC
WARN
SPGDB P/S
FAIL
+5V - LOGIC
+/-15V - LOGIC
+/-24V - LEM
+12V - SCANport
+15V - TACH
6
20V
AC/DC
Converter
56 V DC
1500 W
DC/DC
FAIL
Pumps
120V, single phase
Pump supply is
XXXV, 3 phase
DC/DC
Converter
Printer
PanelView
relays
20 V
Isolated
Gate Driver
Power Supply
(Optional)
Figure 6.45 – Standard PowerFlex 7000L Control Power Distribution (without UPS option)
Figure 6.46 illustrates the extended ride-through capabilities of the
control circuit. An UPS must be installed to provide the energy to
supply the AC/DC converter for an extended period of time in case
of a loss of control power. It is assumed that if control power is
interrupted, the medium voltage will also be interrupted and the drive
will not be required to operate the motor until both control and
medium voltage is re-applied.