Drive Logic Command
Drive Logic Command Word – Database 2.001
The following is the Logic Command from the output of the Parser.
It is a READ only variable in the Drive.
Bit
Function
Value
Description
Notes
0
Stop Command
0
Stop
1
Start Command (pulsed)
1
Start on Rising Edge only
2
Jog
1
Jog at preset speed
3
Clear Fault Queue
1
Clear Fault Queue
4
Clear Warning Queue
1
Clear Warning Queue
5
Drive Reset
1
Reset All Alarms (Faults and Warnings)
6
Direction
1
Reverse Rotation
0
Forward Rotation.
7
Start Profile
0
Accel 1 (Default)
Must be maintained until at
Speed.
1
Accel 2
8
Stop Profile
0
Decel 1 (Default)
Must be maintained until Drive
stopped.
1
Decel 2
10,9
Not Used
12,11
Synchronization
0 0
No command
0 1
Transfer to Line (Bypass)
1 0
Transfer to Motor
1 1
Illegal. Ignore this command
13
Force Stop
1
Force a Stop to the Drive
DPI Forced on Network Errors
14
Force Fault
1
Force a Class2 Fault in the Drive
DPI Forced on Network Errors
15
Not Used