Operator Interface 3-37

7000 “C” Frame

7000L-UM300I-EN-P – June 2013

Modify Parameters

To change a parameter,

Use the up/down arrow keys on the SETUP

screen to select the 'Parameters' option and press the [enter] key.

This will begin the selection process of a parameter as described in
the section entitled "Select a Parameter". The selection process to
change a parameter can also be initiated while displaying the
members of a parameter group on the DISPLAY screen (Figure
3.68) by pressing the [F7] key.

When you have successfully selected a parameter, one of three
possible screens will be displayed depending on the type of
parameter.

Numerical Value

When the parameter is a numerical value, the MODIFY
PARAMETER screen typical of

Figure 3.42

will be displayed. This

screen shows:


the name of the parameter for which you are making the changes

(i.e. Rated motor volt).

the tag code for the parameter, (i.e. 22).

the minimum and maximum allowable limits to which the

parameter must be set, (i.e. 4000 to 4160).

the units in which the parameter data is being displayed

the actual value of the parameter contained in the drive.

Figure 3.42 – Parameter Data Entry