6-136

Component Definition and Maintenance

7000L-UM300I-EN-P – June 2013

7000 “C” Frame


 Clean all contaminated components using a vacuum cleaner

(DO NOT use a blower), and wipe clean components where
appropriate.

 Check for coolant leak at all connections, visually and by touch

wherever possible.

Carry out the physical inspection and verification for the

proper operation of the contactor/isolator interlocks, and
door interlocks.

 Carry out the physical inspection and verification for the proper

operation of the key interlocks.

 Physical verification of the additional cooling fans mounted in

the AC Line Reactor cabinet, Harmonic Filter cabinet for
mounting and connections.

 Carry out the cleaning of the fans and ensure that the ventilation

passages are not blocked and the impellers are freely rotating
without any obstruction.

 Carry out the insulation meggering of the drive, motor, isolation

transformer/line reactor, and the associated cabling.

 Refer to User Manual, Chapter 6 – Component Definition and

Maintenance for meggering procedure.

 Check clamp head indicator washers for proper clamp pressure,

and adjust as necessary.

 Refer to User Manual, Chapter 6 – Component Definition

and Maintenance for details on proper clamp pressure.