Operator Interface 3-41

7000 “C” Frame

7000L-UM300I-EN-P – June 2013

Figure 3.48 – Modify Bit Encoded Value

To be allowed to make changes to the parameter, the

operator

interface must

be set to an Access Level

other than

'Monitor'. (You

will be able to view the screen

;

however, pressing the data entry

keys will have no effect). If you are not in the correct level, press
the [F8] key in order to gain access to the parameter. Refer to the
section entitled Enter/Modify an Access Level

for further

information on the operation to change the level.

Having gained access, press the left/right cursor keys to move to the
various bits within the parameter. As each bit is selected, the name
of the bit is displayed. Use the up/down arrow keys to toggle the
state of the bit.


The new value is not sent to the drive until you exit the screen with
the [F10] key. Prior to this you can modify the new value by
repeating the above procedure, or you can cancel the change by
pressing the [F7] key. The CANCEL operation returns the new
value to that of the actual value.

Analog Ports


The drive contains a number of external analog ports to which you
can assign any parameter.

To setup an analog port, use the up/down

arrow keys on the SETUP screen to select the 'Analog' option and
press the [enter] key.


This will display a screen as shown in Figure 3.49 . The screen
shows the current tags and their tag code, which are associated with
each of the analog ports. To change the tag attached to a port, use
the [cursor up] and [cursor down] keys to highlight the desired port
and press the [enter] key. (If nothing happens then you have not
gained the required access to make changes. Exit to the SETUP
screen and refer to the section entitled

Enter/Modify an Access

Level

to gain access).