Operator Interface 3-61
7000 “C” Frame
7000L-UM300I-EN-P – June 2013
Starting the Trace
The changes do not take affect, and the trend is not started until you
press [F10] and exit the screen. Any time prior to this you may
cancel all the changes made after coming to the screen by pressing
the [F7] key.
When you exit the screen, the trend is started and the screen such as
Figure 3.83 will show the trigger condition and the status. Pressing
the [F7] key on the DIAGNOSTICS screen may also start the trend.
Figure 3.83 – Diagnostic Armed
Figure 3.84 – Diagnostic Triggered
Once the data has started to be collected, the status will show
'triggered' as in Figure 3.84. When the buffer contains a complete
capture, it will show “stopped” (if a single capture), as shown in
Figure 3.85. The time and date at which the trigger occurred is
displayed. The trend buffers may only be viewed when their status
is „stopped‟. If in continuous mode, the capture will stop when the
buffers are viewed. To view the trend buffers, press the [F9] key.