Preparation for downloading firmware – Rockwell Automation 7000L PowerFlex Medium Voltage AC Drive (C Frame) - Classic Control User Manual
Page 449

Component Definition and Maintenance 6-105
7000 “C” Frame
7000L-UM300I-EN-P – June 2013
Required
Ensure the parameters are saved to
Laptop loaded with Windows HyperTerminal program
A null-modem cable with a 9-pin female connector for the
laptop serial port, and a 9- pin male connector for the CIB
Communication Port (J8). (A serial cable with pins 2-3
swapped at one end will also work)
Latest copy of the drive firmware file (filename.XFW)
Drive Access level must be at least „Advanced‟ or higher
(Service or Rockwell).
Here is a typical pin out of a complete null-modem cable
Saving Original Settings
Ensure the parameters are saved to NVRAM, and saved to the
Operator Interface Terminal, and saved to any other external source
such as the Flash Card, DriveTools, or printed to a hardcopy.
Hit F10 (Access), and highlight Advanced. Press Enter and you
should have Advanced level access.
Preparation for
Downloading Firmware