4-52

Commissioning

7000L-UM300I-EN-P – June 2013

7000 “C” Frame




V4

V11

Pump 1

Pump 2

V5

V12

V3

V1

V4

V11

Pump 1

Pump 2

V5

V12

V3

V1

Figure 4.19 – Cooling Cabinet Overview showing Valve Locations – 2



Follow these steps to fill the system:

1. Attach transfer pump to drain/fill line (see drain/fill pump in

Figure 4.20). The inlet is on the left and the outlet is on the right
when the pump is mounted as shown in Figure 4.20. (See flow
direction arrow on Figure 4.20.)