Troubleshooting

7-41

7000 “C” Frame

7000L-UM300I-EN-P – June 2013

WARNING

MESSAGE

WARNING

CODE

DESCRIPTION

RECOMMENDED ACTIONS

Invld Mstr R

344

Invalid Master request-slave only

– Drive tried to become master when

another master was already active

Iso Fn1 Cntr

329

Isolation Transformer Fan 1 contactor

– Isolation transformer Fan 1 status is

NOT HIGH while the drive asked the
contactor to be closed.

Iso Fn2 Cntr

330

Isolation Transformer Fan 2 contactor

– This warning occurs when the drive

commands the Isolation Transformer

Fan 2 contactor to close, and does not
detect the status feedback from the
contactor.

Iso Fn1 Loss

331

Isolation Transformer Fan 1 Loss

– This warning occurs when the drive

detects a loss of pressure or a loss of
Fan 1 contactor feedback when running
on Fan 1.

Iso Fn2 Loss

332

Isolation Transformer Fan 2 Loss

– This warning occurs when the drive

detects a loss of pressure or a loss of
Fan 2 contactor feedback when running

on Fan 2.

IsoTx Air Filter

(A-Frame Only)

26

The Pressure sensed by the pressure
transducer in the integral Isolation
Transformer section (as a voltage) has
dropped below the value set in Pressure

Value Transformer Warning (P655).

– Verify fan rotation
– Blocked airflow in the filters / ducting (if

installed) – Clean as required

– Improper Warning settings – Verify

Pressure Value voltage level when
running with clear air flow

– Verify Alarm and Trip set-up procedure

was completed adequately and adjust as
necessary

– Verify for drives with external ducting that

there is sufficient air to the drive input

– Verify supply voltage to pressure

transducer, and confirm output is stable

IxoTx Fan On

328

Isolation Transformer Fan ON warning

– Isolation transformer Fan status is high

while it should be low.

L Comm Low

55

Indicates that the Autotune Lc (P217)
measured was less than 0.02 pu and the L
Commutation (P140) will have to be tuned

manually.

– REFER TO THE POWERFLEX 7000

SERIES B MANUAL (CHAPTER 4 –
COMMISSIONING) ON AUTOTUNE

PROCEDURES, RESULTS, AND
ACTIONS

L Comm High

56

Indicates that the Autotune Lc (P217)
measured was greater than 0.15 pu and the
L Commutation (P140) will have to be tuned
manually.

Advertising