6-120

Component Definition and Maintenance

7000L-UM300I-EN-P – June 2013

7000 “C” Frame

8. Press Enter key again. The display will change to the

„Diagnostics Setup‟ screen and the desired parameter gets
assigned to Trace 1. Now, press the down arrow key to move the
cursor to Trace 2 and repeat steps 3 – 8 above to assign a
parameter to Trace 2.

9. Repeat above steps until you have assigned the desired

parameters to all the traces from Trace1 to Trace8.


10. Now press F9 [TRIGGER] key. The first letter in the second line

on the screen will toggle between C and S. The letter C stands
for Continuous and S stands for Single shot. Select S for single
shot.


11. Press F2 [CONDITION] key. The cursor will move to the “=”

equal sign. This defines the trigger condition. Press up or down
arrow keys to select + sign as the trigger condition for our
example.