Component Definition and Maintenance 6-37

7000 “C” Frame

7000L-UM300I-EN-P – June 2013

Matched Set 2 SGCTs

Module Housing

Outlet Manifold

Clamp Base

Matched Set 2 SGCTs

Clamp Head

Inlet Manifold


Figure 6.30 – Cooling System


Reconnecting the Coolant System to a PowerCage Module

1. Ensure all power is off and locked-out, including the pumping system.

2. Ensure a blanket or plastic sheet is covering the devices below the

PowerCage being serviced. Face shield and full arm chemical resistant
gloves should be worn at all times when performing this task.

3. Attach both the inlet and outlet manifolds to their bracketry, be sure

to close all the pipe clamps.

4. If necessary, remove the device blocking the left outlet hose and

reconnected it to the lower nipple on the chill block to the extreme
left. Make sure to tighten the hose clamp. Repeat this step for all
outlet hoses and than all inlet hoses.

5. Replace all SGCT/SCR devices and circuit boards as described in

“Replacing the Silicon Controlled Rectifier” and “SGCT
Replacement”.

6. Check coolant levels to ensure there is still enough coolant in the

system. If coolant must be added, see “Adding Coolant” in the
“Cooling Cabinet Components” section.